Series 60 DDEC VI Troubleshooting – Section 13.5 Fan Belts Are Incorrectly Adjusted

Section 13.5
Fan Belts Are Incorrectly Adjusted

To determine if misadjusted fan belts are causing high engine coolant temperature, perform the following: ‪

  1. Test fan belt(s) tension; refer to appropriate service manual, preventive maintenance chapter.
  2. Compare tension to belt specifications listed in Table "Fan Belt Tension" .
    1. If the belt(s) tension is within specification, check the thermo-modulated fan; refer to "13.6 Inoperative Thermo-Modulated Fan" .
    2. If the belt(s) tension is not within specification,refer to "13.5.1 Belt Tension Resolution" .
    3. Single Belt, N (lb)

      2 or 3 Belts, N (lb)

      355 - 445 (80 - 100)‪

      266 - 355 (60 - 80)‪

      Table 1. Fan Belt Tension

Section 13.5.1
Belt Tension Resolution

Perform the following steps to resolve incorrect belt tension:‪

  1. Readjust belt(s) tension as necessary; refer to appropriate service manual, preventive maintenance chapter.
  2. Verify belt tension resolution; refer to "13.5.1.1 Test Engine with Correct Belt Tension" .
Section 13.5.1.1
Test Engine with Correct Belt Tension

Perform the following to determine if exterior radiator repair resolved high engine coolant temperature: ‪

  1. Start and run the engine.
  2. Run the engine through its operating range with no-load for approximately 5 minutes, allowing the engine coolant to reach normal operating range.
    1. If the engine coolant temperature is 88-96°C (190-210°F), no further troubleshooting is required. Shut down the engine.
    2. If the engine coolant temperature is not 88-96°C (190-210°F), shut down the engine. Check thermo-modulated fan; refer to "13.6 Inoperative Thermo-Modulated Fan" .


EPA07 Series 60 DDEC VI Troubleshooting Guide - 6SE567
Generated on 10-13-2008

Leave a Reply

Your email address will not be published. Required fields are marked *