Section 5.22
PID 106, FMI 3, Flash Code 67, Manifold Absolute Pressure Sensor Input Voltage High
The Manifold Absolute Pressure Sensor input voltage is high due to a short.
Section 5.22.1
Troubleshooting PID 106, FMI 3, FLASH CODE 67
Troubleshoot as follows:
NOTICE: |
To avoid damage to the harness and connectors when disconnecting harness connectors, ensure the pulling force is applied to the connectors and not to the wires extending from the connectors. |
- Check wire 432 (light green, manifold air pressure) cavity P-1 in the Engine Sensor Harness (ESH) 30–pin connector for a short to wire 416 (gray, sensor supply voltage, 5VDC) cavity W-1 in the ESH 30–pin connector (see Figure
"Engine Sensor Harness 30–pin Connector"
). If there is a short, repair or replace the wire(s), pins, and sockets.
Figure 1. Engine Sensor Harness 30–pin Connector
- If the code is still active, go to step .
- If the code is not active, Refer to "5.22.2 Verification" .
- Also check pin C (manifold air pressure ) and pin B (sensor supply, +5VDC) in the MAP Sensor connector. If there is a short, repair or replace the wire(s), pins, and sockets.
- If the code is still active, call Detroit Diesel Technical Service.
- If the code is not active, Refer to "5.22.2 Verification" .
Section 5.22.2
Verification
Verify troubleshooting as follows:
- Check the DDR to see if PID 106, FMI 3, Flash Code 67 is still active.
- If the code is still active, go to step 2.
- If the code is not active, troubleshooting is complete.
- If the code is still active, call Detroit Diesel Technical Service.
Series 50G and 60G Troubleshooting Guide - 6SE482 |
Generated on 10-13-2008 |